§ 5-6-124. Passive system requirements.
(a)
Grease traps. The size, type and location of each grease trap shall be approved by an official designated by the authority. Grease traps of pre-cast or poured in-place concrete shall be constructed of sound durable material, not be subjected to excessive corrosion or decay, and shall be water and gas tight.
(b)
Grease interceptor. A grease interceptor shall be sized and engineered based upon the anticipated load and/or conditions of actual use. A grease interceptor shall receive grease laden waste discharge from major point sources. A floor drain shall not be considered a major point source.
(c)
Grease interceptor capacity. A grease interceptor shall have the grease retention capacity for the flow rates indicated in Table 1 set forth below in subsection (d).
(d)
Rate of flow controls. A grease interceptor shall be equipped to control the rate of flow as set forth in Table 1.
TABLE 1
Grease Interceptor Capacity, Sizing and Rating
Sizing Symbol 4 7 10 15 20 25 30 35 50 75 Flow Rate GPM 4 7 10 15 20 25 30 35 50 75 L/S 0.25 0.44 0.63 0.95 1.26 1.58 1.89 2.20 3.16 4.73 Retention
CapacityPound 8 14 20 30 40 50 60 70 100 150 Kilograms 3.6 6.4 9.1 13.6 18.2 22.7 27.3 31.8 45.4 68.2 (Ord. No. 4501, 10/13/07, Sec. 1)